3.1.1. Standard Efficiency Horizontal Water Source Heat Pump TRANE Mode GEHK03641*0KB0BRJ011102210000000000001A, or equal (Qty 1) 3.1.1.1. WSHP must be 3 Ton. 3.1.1.2. WSHP must be HP-30. 3.1.1.3. WSHP must have a Back Supply Air Arrangement. 3.1.1.4. WSHP must have a Right Return Air Arrangement. 3.1.1.5. WSHP must have Variable ECM – Constant Torque Supply Fan Motor. 3.1.1.6. WSHP must be 460/6/3 phase power supply. 3.1.1.7. WSHP must have Copper Heat Exchanger 3.1.1.8. WSHP must have 35 Deg F Protection. 3.1.1.9. WSHP must have Wall Mounted Thermostats. 3.1.1.10. WSHP must have Condensate Overflow Sensor. 3.1.1.11. WSHP must have Entering Water Sensor. 3.1.1.12. WSHP must have United Mounted Disconnect. 3.1.1.13. WSHP must have Matte Faced Insulation 3.1.1.14. WSHP must use 2” Throwaway Filters. 3.1.1.15. WSHP must have a Single Point Power. 3.1.1.16. WSHP must have Enhanced Sound Attenuation. 3.1.1.17. WSHP must have Non-ducted Filter Rack. 3.1.1.18. WSHP must have a Polymer Drain Pan. 3.1.1.19. WSHP must have TRANE SYMBIO 400B with Air Fi. 3.1.1.20. WSHP must have a minimum of a 5-year Compressor Warranty. 3.1.1.21. WSHP must have a minimum of a 2-year Refrigerant Circuit Warranty. 3.1.1.22. WSHP must have a minimum of a 1-year Labor Warranty. 3.1.2. Standard Efficiency Horizontal Water Source Heat Pumps TRANE Mode GEHK03671*0KB0BRJ011102210000000000001A, or equal (Qty 2) 3.1.2.1. WSHP must be 3 Ton. 3.1.2.2. One WSHP must be HP-8 and the other HP-18. 3.1.2.3. WSHP must have a Back Supply Air Arrangement. 3.1.2.4. WSHP must have a Right Return Air Arrangement. 3.1.2.5. WSHP must have Variable ECM – Constant Torque Supply Fan Motor. 3.1.2.6. WSHP must be 265/60/1 phase power supply. 3.1.2.7. WSHP must have Copper Heat Exchanger 3.1.2.8. WSHP must have 35 Deg F Protection. 3.1.2.9. WSHP must have Wall Mounted Thermostats. 3.1.2.10. WSHP must have Condensate Overflow Sensor. 3.1.2.11. WSHP must have Entering Water Sensor. 3.1.2.12. WSHP must have United Mounted Disconnect. 3.1.2.13. WSHP must have Matte Faced Insulation 3.1.2.14. WSHP must use 2” Throwaway Filters. 3.1.2.15. WSHP must have a Single Point Power. 3.1.2.16. WSHP must have Enhanced Sound Attenuation. 3.1.2.17. WSHP must have Non-ducted Filter Rack. 3.1.2.18. WSHP must have a Polymer Drain Pan. 3.1.2.19. WSHP must have TRANE SYMBIO 400B with Air Fi. 3.1.2.20. WSHP must have a minimum of a 5-year Compressor Warranty. 3.1.2.21. WSHP must have a minimum of a 2-year Refrigerant Circuit Warranty. 3.1.2.22. WSHP must have a minimum of a 1-year Labor Warranty. 3.1.3. Standard Efficiency Horizontal Water Source Heat Pump TRANE Mode GEHK048B1*0KB0BRJ011102210000000000001A, or equal (Qty 1) 3.1.3.1. WSHP must be 4 Ton. 3.1.3.2. WSHP must have a Back Supply Air Arrangement. 3.1.3.3. WSHP must have a Right Return Air Arrangement. 3.1.3.4. WSHP must have Variable ECM – Constant Torque Supply Fan Motor. 3.1.3.5. WSHP must be 460/60/3 phase power supply. 3.1.3.6. WSHP must have Copper Heat Exchanger 3.1.3.7. WSHP must have 35 Deg F Protection. 3.1.3.8. WSHP must have Wall Mounted Thermostats. 3.1.3.9. WSHP must have Condensate Overflow Sensor. 3.1.3.10. WSHP must have Entering Water Sensor. 3.1.3.11. WSHP must have United Mounted Disconnect. 3.1.3.12. WSHP must have Matte Faced Insulation 3.1.3.13. WSHP must use 2” Throwaway Filters. 3.1.3.14. WSHP must have a Single Point Power. 3.1.3.15. WSHP must have Enhanced Sound Attenuation. 3.1.3.16. WSHP must have Non-ducted Filter Rack. 3.1.3.17. WSHP must have a Polymer Drain Pan. 3.1.3.18. WSHP must have TRANE SYMBIO 400B with Air Fi. 3.1.3.19. WSHP must have a minimum of a 5-year Compressor Warranty. 3.1.3.20. WSHP must have a minimum of a 2-year Refrigerant Circuit Warranty. 3.1.3.21. WSHP must have a minimum of a 1-year Labor Warranty.