DRAWOUT CIRCUIT BREAKER, SQUARE D MASTERPACT, NW40H2, YA5KKR64A3CFFFXSCA, AS SPECIFIED. 1.1 3-Pole ANSI C37 / UL 1066 Rated 1.2 Rated 4000 Amps, 100% Rated 1.3 AIR - 85kA/85kA/85kA@ 254/508/635 Vac 1.4 4000 Amp Sensor Plug 1.5 UL Type A Plug 1.6 Trip Unit Type 6.0P with: Zone Selective Protection (LSI} 1.7 Residual Ground Fault Protection 1.8 Ground Fault Trip Only 1.9 Power Meter 1.10 Modbus Communication Module 1.11 Eight (8) Auxiliary Contacts 1.12 Spring Charging Motor - 100-130Vac 1.13 Shunt Trip - 100-130Vac 1.14 Closing Coil - 100-130Vac 1.15 2nd Shunt Trip - 100-130Vac 1.16 Overcurrent Trip (SOE} contact standard 1.17 Padlockable Push Button Cover 1.18 Open position padlock provision - No locks supplied with Padlock attachment 1.19 Automatic Spring Discharged Interlock Standard.