To purchase a Portable Load Bank with digitally controlled infinite loads, ramp-up and ramp-down operations, and mobility and transportation features. The unit provided must meet or exceed the following features and specifications. Reference: Simplex Infinity 200 Digital Load Bank or Department approved equal. TECHNICAL SPECIFICATIONS: Power Capacity: • 200 kW at 240V and 480V, 3-phase • 150 kW at 208V and 416V, 3-phase • 133 kW at 240V, single-phase; Load Type: Resistive type. Frequency: 50 Hz, 60 Hz. Voltage Compatibility: Automatic calibration for applied voltage, supporting intermediate voltages (440V, 416V, 220V, 208V). Network Capability: Ability to daisy chain up to 40 units with a total capacity of 8,000 kW. Unit to have continuous-duty operation capability. Control System: Single-point control of the load banks with a master handheld touchscreen controller using RS-232 connectivity. Data Acquisition: Digital power transducer with display capabilities for volts, amps, frequency, and kW...