A. At Mount Olive Correctional Complex and Jail, the existing chillers, chiller controls, pumps, and pump controls were installed in 2012. The existing chillers and chiller controls are located outside on a concrete pad. The existing chiller pipes goes underground from the sides of the existing concrete pad to just right inside building G. Then, the chiller pipes are installed up the inside wall and along the ceiling area into mechanical room 216. In room 216, the pumps and pump controls are located. From the pumps, the chilled water flows in the chiller pipes throughout several building areas. The chillers provide air conditioning to multiple building areas at the facility. The contractor must replace the existing two (2) chillers and chiller controls, four (4) butterfly valves, any required piping, four (4) pumps and pump controls, and any associated parts and install new. B. Below is additional information on the existing chiller units with chiller controls, pump controls, pumps, water softener, by-pass & filter feeders, butterfly valves, and electric actuators: 1. Below is information on the existing chiller units: a. Manufacturer: York. b. Size: one hundred ninety-six (196) tons c. Type: Air cooled screw liquid chiller d. Model no.: YVAA0213ADF46BA e. Serial no.: SBYM-242200 and SCYM-242230 f. Voltage: 460 volts, 3-phase, 60 hertz g. Refrigerant R-134a h. Refrigerant pipe size: Six (6”) 2. Below is information on the existing controls: a. Intellipass Integrated Drive Bypass: Secondary Pump No. 1 and 2: 1) Manufacturer: Eaton 2) Cat no.: VS0240411A-00000 3) Style no.: VS020411A-00000 4) Software code: G.O. no.: JNCT15089-01, Date Code: 122603 5) Input: 480 V, 3 phase, 50/60 Hz 27 A RMS 6) Output: 0 to 480 V, 3 phase, 1 to 320 Hz 27 A RMS 7) Max ambient: 40 degrees Celsius 8) Nominal HP: 20 VT Overload :1.10 9) Enclosure: NEMA Type 1 with Intellipass 10) Grounding is required 11) Serial no.: 12830243 and 12830245 b. Intellipass Integrated Drive Bypass: Primary Cold Water Pump No. 1 and 2: 1) Manufacturer: Allen-Bradley 2) Cat no.: 513-AAB-3-6P-39 3) REV: 15 – 61 4) SER: 1 5) Wiring diagram: CC20006147 6) Line: 480 V 7) Control: 120 V 8) NEMA size: 0 9) Enclosure type: 1 c. VFD Fuse Blocks: 1) The metal cabinet was not opened.