1. (1) Installation of a 120 ft. SS Rev I Freestanding Saber Tower S3TL or equivalent, with concrete foundation/pad. Tower and pad need to be engineered for 180’ tower (future expansion). a. The Tower will be designed in accordance with EIA 222H Engineering Standards also to include an ice bridge.5r b. Install nine (9) customer supplied Antennas and (2) microwave dishes * 6ft. microwave dish with supporting ice shield at 50’ * 4ft. microwave dish with supporting ice shield at 20’ * Seven (7) dipole antennas installed at 110ft. * Two (2) dipole antennas installed at 80ft. c. All Tower Steel will be Hot Dip Galvanized. Engineering Drawings to be sealed by a registered NM Professional Engineer. d. Tower to Include Climbing Ladder, Safety Climb Device, and Waveguide Ladder with both ¾ inch and 3/8 inch holes to support all lines. With nine (9) runs of 7/8” heliax cable. e. Grounding of the tower site meets R56 standards. f. Unterminated runs to be weather protected. g. Tower will not be required to have FAA lighting. 2. (1) 12x16 Thermobond or equivalent enclosed shelter made of fire-resistant material with; a. a concrete foundation/slab. b. Shelter to include an integrated HVAC unit and; c. a 200-amp Service Panel; d. A cable tray installed on the inside the building on the ceiling the length of the building. e. Ground buss bar to be installed inside the building f. Grounding of the building to meet R56 standards 3. Grounding/bonding on tower site and building to meet R56 Standards...