Project includes removing generators and ATS from two pump stations and installing a new Cummins generator, ATS, and MTS at each location while keeping all City infrastructure in power with only minimal agreed upon downtime. The City will be providing the Cummins generators, ATS, and MTS. 1x 100KW, 1x 150KW.Work is performed at sites in close proximity to other businesses, homes or agencies and work will need to be performed in a manner that has limited impact on parking, traffic or other activities. Any impacts will need to be clearly communicated to and with collaboration to the surrounding impacted business or agency. These 2 projects are at separate locations and shall be done one at a time but sequentially. a) Power Distribution: i. Includes providing temporary power and communications via contractor provided temporary ATS and cables, drive over wire chase and using City provided mobile genset. ii. Includes removing old ATS. iii. Includes installing new (City supplied) ATS and MTS at each location. iv. Includes all required mounting hardware for electrical equipment. v. Includes grounding of new electrical equipment. vi. Includes conduit and wire to feed new electrical equipment. vii. Includes trenching and underground work to serve new generator...