Specifications include, but are not limited to: The Jefferson County Department of Health (JCDH) seeks a contractual Life Safety Inspection and Maintenance Service to provide safety inspection and Maintenance services at all the JCDH locations as listed in the specifications. The bid consists of various health centers to be serviced. Fire Pump-To include an inspection of the pump equipment (pump, driver, controller, piping, valves, etc.); installing calibrated test gauges (suction & discharge); flowing water thru the flow meter (header requires the use of a flow device); water is flowed at three critical points; churn (no flow), rated (100%), and peak (150%), the following readings are taken at each point, discharge pressure, suction pressure, RPM’s, volts and amps; the net pressure is calculated.