Contractor shall provide labor and materials for the following: Room 3616 – Install new locking L6-50 outlet, connect to panel 2EMFP and install new breaker. Room 3527 – Purchase and install buck boost transformer that will deliver 240V 30 amp for a new Hi-Temp Pyro-Clean oven. Provide properly sized breakers and connect to Oven. Room 2416 – Convert L6-30 outlet to L5-30 outlet. Replace breaker in panel 2 WPH. Remove excess or no longer used conductor. Replace conductors and conduit if required to meet code. Room 2512 – Install two (2) new 5-20 duplex outlets, connect to panel 2WPUand install new breakers. Room 2319 – Move two (2) 5-20 outlets to emergency power (from regular power panel 2WPT to 2EMDE). Room 2320 Move 5-20 outlet to emergency power (from regular power pane 2 WPT to 2EMDE) Room 2128 – Install new 6-15 outlet, connect to panel 2EMCB and install new breaker. Room 2129 – Install two (2) new 5-20 outlets, connect to panel 2EMCB and install new breakers. Room 2130 – Install new 5-20 outlet, connect to panel 2EMCB and install new breaker. Room 2122 – Convert 6-20 outlet to 5-20 outlet. Replace breaker in panel 2EMCB. Remove excess or no longer used conductor. Replace conductors and conduit if required to meet code. Room 2121 – Install new 5-20 outlet, connect to panel 2EMCB and install new breaker. Room 2118 – Replace 5-15 duplex outlet with 5-20 duplex outlet.