1. 2 return line solenoids (1 on 8k tank and 1 on 10k tank) need to be replaced with AC voltage solenoids. The current ones are DC voltage. This was at the request of our controls’ technician from Johnson Controls (Chris Cain). The install and programing will need to be coordinated with JCI to insure proper functionality. 2. Remove unused Solenoid and bypass on 10,000-gallon tank. Replace with straight pipe run and paint to match. (See Photo) 3. Troubleshoot Fuel pump 1 on Tank 1 4. Troubleshoot fuel polisher on Tank 1 (8k Tank) 5. Add new starters with Hand/ OFF/ Auto functionality, for Fuel pumps 1 and 2 located in Data Center generator room. (See photo) 6. Replace current fuel monitor system with EVO 200. New system will be mounted in Switchboard C room located in C-Building. 7. Run new conduit for power, fuel probes, and communications on new fuel monitor. 8. Program new EVO Fuel management system to communicate with Metasys BAS system on Solenoid controls for high level alarms. 9. Replace diesel fuel piping for Generator C that is being pushed up due to heaving concrete from underneath. Re-run new pipe with minimum 6-inch clearance. (See Photo)