1. Follow the manufacturer's preventative maintenance schedule as per the exact UPS models: SCOM-UPS-01 SCOM-00-0028 Eaton 93PM; COLE-UPS-01 COLE-00-190A Vertiv Liebert EXM; UNIV-UPS-01 UNIV-06-6036 MGE UPS System, Galaxy PW; UNIV-UPS-02 UNIV-06-6036 MGE UPS System, Galaxy PW; CHPN-UPS-01 CHPN-00-G25B Myers, Illuminator Central Inverter System; SBUS-UPS-01 SBUS-00-0091 Emerson Network Power, Leibert NX; OVLK-UPS-01 OVLK-03-3725 Eaton 93E. 2. Review and download the alarm log(s) for the report. 3. Run all system diagnostics programs and correct any issues. 4. Replacing, with new, all UPS, air flow, cooling filter elements annually. 5. Conduct a visual inspection of the UPS, ensuring the overall environment is clean, free of dust and debris. Vacuum PC boards and cabinets, wipe down cabinets and batteries. 6. Conduct a visual inspection of the UPS system capacitors for signs of fluid leak. 7. Examine and evaluate the room’s ventilation system and temperature to confirm operation. 8. Scroll through all UI screens to check for proper operations. 9. Conduct a visual battery inspection to look for indications of leaks or swelling. 10. Measure the batteries ambient temperature...