1.1 SUMMARY A. Section Includes: Two (2) 30-ton, packaged, small-capacity, rooftop mounted air-conditioning units. 1.2 ACTION SUBMITTALS A. Product Data: For each Air Handling Unit. 1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes. 2. Include rated capacities, dimensions, required clearances, characteristics, furnished specialties, and accessories. 3. Include unit dimensions and weight. 4. Include cabinet material, metal thickness, finishes, insulation, and accessories. 5. Fans: a. Include certified fan-performance curves with system operating conditions indicated. b. Include certified fan-sound power ratings. c. Include fan construction and accessories. d. Include motor ratings, electrical characteristics, and motor accessories. 6. Include certified coil-performance ratings with system operating conditions indicated. 7. Include filters with performance characteristics. 8. Include gas furnaces with performance characteristics. 9. Include dampers, including housings, linkages, and operators.