A. Submit shop drawings showing details of construction and erection for each tank as follows: 1. Dimensions of tank, fittings, and attachments, with bolt and gasket material. 2. Locations of fittings and attachments and size of manway openings. 3. Wall thickness calculations for each tank. Calculations shall be per ASTM D 1998-99 using 600 PSI design hoop stress @ 100º F. 4. Resin used and a complete manufacturers specification of the resin use. 5. Knuckle radius. 6. Weight of tank. 7. Corrosion data for all materials in contact with the chemicals. 8. Certificate of Compliance from the tank manufacturer stating: A. All fittings, heat tracing, insulation, et cetera, have been installed by the tank manufacturer. B. H20 tests have been performed by the manufacturer and all fittings were installed prior to H20 tests. C. All tanks are designed and manufactured in accordance with ASTM-D 1998 Type 1. 9. Details on tank packaging.