Specifications include, but are not limited to: This contract shall include one (1) annual on-site inspection per each portable fire extinguisher on the University campus. The annual inspection shall be performed by an employee of the Contractor who has undergone the instructions necessary to reliably perform maintenance and has the manufacturer's service manual for the fire extinguisher. The Annual Maintenance is a thorough check of the extinguisher to include a thorough inspection of the three (3) basic elements of the extinguisher: (a) mechanical parts; (b) extinguishing agent, and (c) expelling means. The Annual Inspection shall include a check of at least the following items: (a) Located in designated place. (b) No obstruction to access or visibility. (c) Hanger or cabinet securely fastened to wall. (d) Operating instructions on nameplate legible and facing outward. (e) Seals and tamper indicators not broken or missing. (f) Determine fullness by weighing. (g) Examine for obvious physical damage, corrosion leakage or clogged nozzle. (h) Pressure gauge reading or indicator in the operable range or position. (i) Removal of expired tags