The scope of work shall consist of furnishing all labor, materials, tools, and equipment necessary or incidental for Service and Maintenance on four (4) Lochinvar KB-801 boilers. Schedule of Maintenance Work to include: 1. Clean and adjust burner 2. Assure positive ignition, adjust and clean as required 3. Determine response to flame safeguard system for monitoring and safety shut down 4. Perform combustion analysis (gas/oil), and adjust fuel/air ratio for optimum efficiency, and supply print out. 5. Check fuel supply(gas/oil) which is affected by pumps, strainers, gauges and regulators 6. Check reliability of low water cut-off, and the operating and limit controls in accordance with the manufacturer’s recommendations 7. Check gaskets on fuel lines, fireside and waterside, and make suggestions for any corrective action required 8. Check and suggest necessary parts for inventory 9. Inspect and assure proper operation of related equipment such as pumps, etc. 10. Any other inspection required per the manufacturers recommendation.