Specifications include, but are not limited to: The Electronic Access Control and Intrusion system work for this project will consist of the following (the contractor shall provide any items not expressly noted as supplied by the City): 1. The Contractor shall use a Vykon JACE (SEC-J-8000) controller based on the Tridium Niagara Framework. Systems that are not developed on the Niagara Framework platform are unacceptable. 2. The Contractor shall configure the JACE security controller to control access, maintain historical records (Audit History, Log History, Badge Swipe Record, and Security History). 3. The Contractor shall configure each JACE controller to communicate to door controllers, gate controllers, and other monitoring alarm input/output devices provided under Division 281000. 4. Each JACE shall communicate to door controllers and other monitoring alarm input/output devices provided under Division 281000 – Electronic Access Control and Intrusion System Specification. 5. The Door Control Module (DCM) shall be a Vykon model SEC-R2R. The DCM shall provide a physical interface for Electronic Access Control Systems (EACS) door peripherals such as card readers, door positions switches, request to exit devices, and output to control the door locking mechanism. The DCM shall communicate directly to the JACE through an RS485 interface. For details information, refer to section 2.5 in the Division 281000 – Electronic Access Control and Intrusion System Specification...