Specifications include, but are not limited to: A. Provide electrically operated equipment designed and built for operation with electric characteristics provided by Division 16. Verify voltage, horsepower, wattage and phase from electrical drawings before ordering equipment. B. Provide motor controls, systems controls, starters, contractors, etc., required for the mechanical systems complete as a part of the motor or apparatus which it operates, unless specifically noted to be provided under another section. C. Provide under the work of this section all other devices, line and low voltage control and interlock wiring, and additional conduit necessary but not indicated on the electrical drawings, all in accordance with material and installation requirements. D. Provide wiring diagrams required for the proper installation of the equipment under the work of this section. E. All mechanical assemblies containing multi-motors or electric heating elements shall be factory equipped with integral over-current protection for each motor/heater in accordance with the requirements of the N.E.C.