Specifications include, but are not limited to: A. The structure must be a Stressed Membrane Structure measuring 40 feet wide by 100 feet long, measured maximum width by maximum length. B. The entire roof slope of the structure, including the peak, shall have a minimum slope of 26 degrees. C. D. E. F. G. H. I. J. TENSIONED FABRIC STRUCTURES 13310-4 ARFF TRUCK SHELTER KAHULUI AIRPORT PROJECT NO. AM1033-17 No exterior guy ropes or cables shall be used for anchoring the structure. There will be no exposed exterior horizontal purlins. The structure shall be completely clear-span with no interior supports of any description. The main structural support beams shall be continuous from the ground seal to the peak and manufactured in such a way that no eave will exist. The structure shall be designed to meet the wind loads as outlines in IBC 2018, 145 mph, exposure ‘D’. For repair cost and expansion efficiency, the structure shall be modular in design consisting of individual membrane panels which do not exceed 12’-6” in width on the main center modules. The structure shall be designed so that any section of architectural membrane may be removed or replaced within four hours using a maximum of four workmen. The structure shall include but not limited to the following features: 1. 2.5' leg extensions 2. Corrosion resistant package 3. Single personnel door(s) complete with hood, high traffic panic & closer (3'0" x 7'0") 4. State of Hawaii DOT - Airports Division graphic logo at entrance 5. Engineered flat end(s) 6. Penetration Kit(s) for non-insulated structures (Medium) 3" to 6" 7. Penetration Kit(s) for non-insulated structures (Small) 1/4" to 4" 8. Turbo ventilator(s) - 24"...