A. Service Frequency Closed loops and geothermal systems will be serviced on a quarterly basis once treated to specifications. Cooling towers will be serviced monthly when in operation. B. Services provided during each service call • Conduct chemical tests on each system (treatment residuals, conductivity, etc.) • Maintain treatment inventory, deliver treatment products to point of use, and add to systems as required. • Check, calibrate and clean conductivity control and chemical feed equipment as required. Inspect equipment for cleanliness and proper operation. • Provide service reports in electronic format listing test results • Provide a method to store technical data and service reports in an electronic format for easy and efficient access by Sumner County school personnel. C. Other Services • Training seminars provided on location as often as need arises. • Deposit analysis and Total Bacteria counts as required to maintain clean heat exchange equipment.