Specifications include, but are not limited to: GENERATOR Emergency, Stationary, Generator to include all installations, labor, materials, permits, and inspections for project: Shall be as follows: Kohler 25kw Natural gas, 120/240 Volt 3 pole, 4 wire generator Weather resistant, sound attenuated enclosure and new 100 Amp 3 pole solid neutral 240 Volt NEMA 3R Enclosure Docking Station Meets NFPA 110, UL2200 listed and EPA Certified Tier 3 standards. Generator set and components prototype tested, and production tested according to the UL test program. ENGINE Model number 25REOZJ, 25KW 120/240 Volt, three phase Delta 75 Amps standby Kohler natural gas fueled engine 2.2 Liter inline 4-cylinder turbo charged. Permanent magnet generator (PMG) Governor electronic Dry type filters Vibration isolators between engine-generator and skid Oil and coolant drain extended to genset base rail. Unit mounted radiator with shell and fan guard 12-volt starter and alternator Starting batteries with cables and mounting tray Battery charger 10 amp 500-Watt block heater, 120 V 1Ph 100 amp main 100% rated 3-pole main line circuit breaker, with Thermal Magnetic and Shunt Trip mounted in connection box. CONTROL PANEL Genset Controller shall be as follows: Model# Kohler APM402 Digital Control Panel NFPA 110 level 1 compatible Emergency stop switch. • Backlit LCD digital display with two lines of 12 characters (see User Interface Displays for menus) • Alarm horn indicates generator set shutdown and warning faults • Environmentally sealed membrane keypad with three master control buttons with lights ◦ Off/Reset (red) ◦ Auto (green) ◦ Run (yellow) • Pushbutton/rotary selector dial for menu navigation ◦ Rotate dial to access main menus ◦ Push dial and rotate to access sub menus.