Specifications include, but are not limited to: GENERATOR Emergency, Stationary, Generator to include all installations, labor, materials, permits, and inspections for project: Shall be as follows: Kohler 100REOZJ, 102kW, 277/480 Volt, 3- phase, 153 Amps standby engine Meets NFPA 110, UL2200 listed and EPA Certified Tier 3 standards. Generator set and components prototype tested, and production tested according to the UL test program Describe: _________________________________ _________________________________ _________________________________ _________________________________ _________________________________ _________________________________ _________________________________ _________________________________ _________________________________ _________________________________ ENGINE John Deere diesel fueled 2.2 Liter 4 cylinder turbocharged. Permanent Magnet Generator (PMG) Electronic governor Dry Type Filters Vibration isolators between engine-gen and skid Oil and coolant drain extended to Genset base rail. United mounted radiator with shell and fan guard 12 Volt starter and alternator Starting batteries with cables and mounting tray Battery charger 10-amp 1500-Watt Block heater, 120V, 1 Ph 175 Amp Main 100% rated adjustable 3-Pole main line circuit breaker with electronic trip mounted in connection box. Generator 1800 RPM brushless type excitation, 60 Hz, three phase, 277/480-volt, thermal overload protection, Class H insulation, direct flex disc drive. 12 Lead with strip heater