Specifications include, but are not limited to: Desired services include: • Provide a natural gas fueled generator that will be installed exterior to the building. • 600 kW, 750 kVA, 902 Amps minimum. • Voltage 277/480v, 3 Phase. • 60Hz, 1800 RPM. • Microprocessor digital controls with LCD display for engine components. Sealed components, digital voltage regulator. • Minimum 2-year, 1,000-hour comprehensive warranty. • Generator Enclosure: Sound Attenuated Weather Proof Enclosure, Level 3, integral lighting, motorized dampers, 100 amp load center, convenience outlet, unit heater, block heater, battery charger. • Remote Annunciator Panel. • Remote Emergency Stop Button, quantity (2). • Circuit Breakers (LSI, 100% Rated): (1) 1,000 Amp, (1) 60 Amp. • Automatic transfer switches: (1) 1,000 Amp 4 Pole Open Transition, (1) 100 Amp 4 Pole Open Transition. Basis of Design: ASCO 7000 Series.