Specifications include, but are not limited to: 1. All horizontal data lines will be Category 6, 450 MHz Plenum cable or better. 2. All copper patch cables will be Category 6, 450 MHz or better. 3. All horizontal wiring and patch cables will be Green in Color. 4. Maximum horizontal run will be 295 feet. 5. Please provide two to ten feet of service loop on the Camera end of the cable where possible. 6. Follow the same EIA/TIA 568A or 568B standard per location. 7. All horizontal data lines will be in j-hooks, wire basket trays, or tied up when above the ceiling or in tunnels. Due to existing wiring, most data paths will already be predesignated. 8. If a data run is in occupied or visible areas, all horizontal wiring will be in conduit, raceway, or moulding up to the ceiling height. If run outside, the conduit will need to terminate directly at the camera. 9. Interior conduit can be plastic 10. An Exterior conduit or equivalent longer than 4 feet must be metal. 11. All conduit, raceway, or molding shall be secured with screws. (ie...No peel and stick) 12. All horizontal wiring will terminate on a patch panel. UFA will provide a Patch Panel if needed. 13. Mounting surface boxes, biscuit boxes, and faceplates are required when possible. 14. When boxes are concealed within a ceiling, an appropriate label will be placed on the ceiling grid to indicate the location of the data connections. 15. Data lines will be labeled on the wire and the box at both ends. 16. A data drop is considered two separate CAT 6 data lines. 17. All Labeling will be in accordance with the UFA Technology Division. 18. All Data lines will be tested, and the results must be emailed to the UFA Technology Division. Types of Preferred Cameras and Wiring Equipment 1. Hitachi or General CAT 6 plenum cable or equivalent or better. 2. Hubbell category 6 modular jacks (Forest Green keystones) or equivalent or better. 3. Copper Patch cables will be Forest Green in color. (2 meter in length) 4. Axis NVR softwware or Axis-compatible software is preferred. 5. All Raceway, Conduit, Boxes, Faceplates, and other accessories must be compatible with another raceway/molding.