Specifications include, but are not limited to: 1. LIGHT FIXTURES SHALL BE MINIMUM 80 CRI, UON. 2. PROVIDE ALL LIGHT FIXTURES WITH DIMMING DRIVERS CAPABLE OF DIMMING DOWN TO 10% WITHOUT FLIKERING, NOISE, OR OTHER DEFECTS IN LIGHTING FUNCTIONALITY, UON. 3. VERIFY FUNCTIONALITY OF ALL DRIVERS WITH LIGHTING CONTROL SYSTEM. 4. WHERE EMERGENCY LIGHTS ARE INDICATED, BATTERY PACK SHALL PROVIDE 90 MINUTES OF BACKUP POWER FOR WATTAGE INDICATED, UON. UPON POWER FAILURE TO INDIVIDUAL ROOM, MULTIPLE ROOMS, OR WHOLE BUILDING, EMERGENCY LIGHT FIXTURE SHALL TURN ON TO 100% OF BATTERY BACKUP OUTPUT REGARDLESS OF LIGHT SWITCH POSITION OR ONBOARD OCCUPANCY SENSOR CONTROL. PROVIDE ANY ADDITIONAL DEVICES REQUIRED TO MEET THE REQUIREMENTS OF NFPA 101. 5. PROVIDE INTERLOCK WITH FIRE ALARM SYSTEM FOR ALL EMERGENCY LIGHT FIXTURES SUCH THAT ACTIVATION OF THE FIRE ALARM SYSTEM ILLUMINATES 100% OF BATTERY BACKUP OUTPUT REGARDLESS OF LIGHT SWITCH POSITION OR ONBOARD OCCUPANCY SENSOR CONTROL. PROVIDE ANY ADDITIONAL DEVICES REQUIRED TO MEET THE REQUIREMENTS OF NFPA 101. 6. FIXTURES SHOWN ARE BASIS OF DESIGN FOR LIGHTING CALCULATIONS. REGARDLESS OF CONTRACTOR SELECTION, CONTRACTOR MUST SUBMIT GENERAL USE AND EMERGENCY LIGHTING DESIGN CALCULATIONS FOR APPROVAL TO ENSURE LIGHTING REQUIREMENTS PER SPECIFICATIONS/CONTRACT DOCUMENTATION AND NFPA 101 ARE MET. FOR CALCULATIONS, LIGHT LOSS FACTOR MUST BE 0.8 AND REFLECTANCES MUST BE THE FOLLOWING: 80% FOR CEILINGS, 50% FOR WALLS, AND 20% FOR FLOORS. 7. ALL EXIT SIGNS SHALL BE UNSWITCHED...