Specifications include, but are not limited to: I. Scope of Work and Community/Climate Data (G Sheet) The project scope of work, community data, climate data and project phasing plan is provided on this sheet. IV. System Schematic and Project Specific Design Criteria (G Sheet) Separate Schematic Sheets should be drawn for water and sewerage systems. The Schematic Sheet will serve as a line diagram of the overall systems. The schematic sheets should include the following: A. Water 1. General perspective view of the entire water system with major features Attachment 7 – VSW Design Review Procedures Page 4 of 11 2. Storage tanks with base and overflow elevations and capacities 3. Major points of use 4. Major elevation references 5. Operational pressures during both minimum and maximum flows B. Well Data 1. Pump House/Washeteria location and note the source of power 2. Date of construction, contractor, well number, and surface elevation 3. Depth and size of bore hole 4. Static water level and the date of measurement C. Sewerage 1. General a. General perspective view of the entire sewerage system designating direction of flow, major features, and force-mains b. Lagoon(s) with the number of cells, capacities of each cell, dimensions, floor elevations, overflow elevations, if applicable c. Community septic tanks with number of chambers, capacities of each chamber, dimensions, and inlet/outlet elevations, if applicable d. Community drainfield information with areas, materials, soil type, percolation rate, and elevations, if applicable e. Outfall lengths, materials, elevations, and diffuser type, if applicable f. Major points of use g. Major elevation references h. All manholes i. All lift stations