Specifications include, but are not limited to:. Chemical control panel for bleed control and injective of chemical is to meet the following minimum requirements:. The Controller must be able to directly monitor and control both the addition of the corrosion inhibitor, the Primary Oxidizing Biocide and the secondary biocide. It must also be able to measure the active polymer in the system. The controller must have the ability to monitor and control conductivity (bleed). Chemical Storage Requirements:. Storage container material of construction must be stainless steel. It must have an appropriate lining if storing corrosive chemical material. Exteriors must be stainless for strength. Secondary containment volume must be at least 150% of the delivered chemical storage container volume. Chemical Delivery Requirements:. Chemical transport equipment must comply with DOT requirements for transporting hazardous material. Chemical transport equipment brought on site must be stainless steel on exterior for strength.