Specifications include, but are not limited to: The required services to be provided are Quarterly, Annual, and Triennial maintenance for CAT 3516 generator, Serial Number LY500619, located at Richmond State Supported Living Center (RSSLC). All maintenance services performed under this scope of work must be in compliance with manufacturers requirements. Quarterly maintenance to include but not limited to: a) Cooling System 1. Inspect Radiator/Heat Exchanger for leaks, damage, or obstructions. 2. Add coolant to bring the coolant to its correct level. Coolant to have proper antifreeze percentage for the generator. 3. Check Supplemental Coolant Additive (SCA) and add as needed. 4. Inspect condition of radiator cap, gasket and sealing surface. 5. Inspect water pump and cooling system gaskets for leaks. 6. Inspect flexible water connections for cracking, leaks and pliability. 7. Tighten all hose clamps. 8. Check belt tension. 9. Inspect belts for cracking and/or fraying. 10. Inspect pulleys for excessive wear.