Specifications include, but are not limited to: Hardware - The system must communicate using GPRS with always-on, continuously connected, always communicating encrypted VPN Connection utilizing private static IP addresses. - The system must send event/alarm messages within 5 seconds of receiving. - Provide a Test/Disable Feature for system maintenance/testing. - Provide at least 14 digital (dry/discrete) contact inputs with 0 to 30 volts range. - Provide at least 2 analog inputs capable of 4 to 20ma or 0 to 5vdc. - Provide at least 4 controllable ground outputs for remote start/stop, on/off control. - Hardware must operate at 12vdc to 24vdc. - Hardware must be magnet mountable. - Hardware must be “Plug and Play” capable with removable terminal blocks, allowing the customer to replace without the need of outside labor, dedicated computers or software for programming. - Hardware must be capable of monitoring any type of equipment. Generator Systems Typical NFPA 110 Alarms/Events (may vary by generator/control manufacturer) - Utility power failure - Generator running - ATS in emergency position - Switch not in auto - Low engine temperature - Pre-high engine temperature - Pre-low oil pressure - Common alarm - Low fuel level - Fuel leak to containment - Low/high battery voltage Sewage Lift Stations - High wet well level - Power Failure