Specifications include, but are not limited to: A. Maintenance TU-2426-SBR – Fire Extinguisher Service - Specifications 1. The Contractor shall perform fire extinguisher services by adhering to NFPA 10 requirements. All extinguishers shall be thoroughly examined or maintained as defined by NFPA 10 in their regular location at intervals of not more than once a year. 2. Inspections, testing and routine repairs procedures shall include checking for the following once per year: (The date of the inspections shall be coordinated with the Contractor and the EHS FSM or assigned designee.) a. Proper pressure and gauge reading b. Broken or cracked hoses and gauges. c. Broken safety seals or pins (tamper indicators) d. Proper charge (fullness by weighing or lifting) e. Clogged nozzles f. Mechanical parts operation g. Extinguishing agent h. Expelling means i. Obstruction to access or visibility j. Date for hydrostatic test. 3. All extinguishers shall be marked with the appropriate inspection tickets on an annual basis. 4. If an extinguisher is in its proper location, and the Contractor overlooks performing the required maintenance and certification on the extinguisher, the Contractor shall be held responsible for performing the required maintenance/certification at their expense. 5. If an extinguisher has been moved from its designated location and the Contractor is unable to perform the required maintenance/certification, the Contractor shall notify the EHS FSM or assigned designee of the missing extinguisher. The cost of re-certification of that extinguisher shall be Towson University’s responsibility.