Specifications include, but are not limited to: The Provider shall supply St. Tammany Parish Facilities Management with a Preventative Maintenance Schedule for the year. For each preventative maintenance visit, Provider shall supply St. Tammany Parish's Facilities Management with a preventative maintenance and inspection report that details the activities of each session, on a per site basis. Provider shall keep a Maintenance log of all activities of the Parish generators. At a minimum the following is required: Major Inspection (1 x a year) shall include the following: • Disable the unit from operating • Check the engine coolant level, adjust as necessary • Check the oil pressure gauge for proper operation • Check the fuel delivery system for leaks and correct pressure, tighten as necessary • Check and record radiator anti-freeze with hydrometer • Check the engine block heater for proper operation • Check the air inlets and outlets for debris, clean as necessary • Check the battery posts, cables and charger for loose connections, corrosion and proper operation • Check the battery electrolyte level and specific gravity if accessible • Check the unit wiring for loose connections, corrosions and damages. Correct as necessary • Check the engine alternator for correct voltage output, visually inspect the unit looking for leaks, damage, loose connections or components, correct as necessary • Test the engine and transfer switch safety devices, correct and/ or adjust as necessary • Initiate an automatic start and transfer of the unit to site load and exercise the unit. Look for any abnormal operating conditions and correct as necessary • Check exerciser clock for proper operation • Start and exercise the unit at full load. Look for any abnormal operating conditions and correct as necessary • Check engine RPM's / Hertz • Change theoil • Replace the engine oil filter(s) • Replace the engine fuel filter(s) and re-prime the fuel system • Replace the engine air filter(s) • Perform a 5-minute no-load operational run of the unit looking for any posts service problems • Return the unit to stand-by setup...