Specifications include, but are not limited to: DPS is seeking a contractor to provide tower decommissioning and new-build services for DPS towers located at various sites throughout the State of Texas. DPS will coordinate with the contractor on the location and type of tower to be decommissioned, and the new-build design requirements. New Tower Requirements: • TIA-222 Rev & Risk Category- this should be Rev H, Risk category, specified upon design requirements. • Height-350 ft, or as specified by location. • Type – SST (Self Supporting Tower) • Equipment Loading Scenario- See attached tower loading sheet • Tower Capacity- Shall be 85% or greater at full load • DPS will specify Site name, address, and coordinates • Shelter requirements: o Concrete, 12 ft x 16 ft. (sample attached) o New or refurbished (sample attached) o Concrete pad required (TBD on site location) o See attached building configuration drawing sample attached for rack configuration.