Specifications include, but are not limited to: (CU 101304) THREE (3) PAIR SHIELDED-CABLE FOR COMMUNICATIONS, CONTROL, AND INSTRUMENTATION APPLICATION. CABLE SHALL BE RATED: THREE (3) TWISTED PAIRS OF #18 AWG, FULLY ANNEALED, STRANDED, TINNED COPPER CONDUCTORS PER ASTM B-33; 300 VOLT OR BETTER,-20 DEGREES TO 90 DEGREES "C" TEMPERATURE RATING OR BETTER, TYPE PC/PLTC (POWER LIMITED TRAY CABLE); MINIMUM 25% OVERLAP FOIL SHIELD PLUS STRANDED, TINNED COPPER #18 AWG DRAIN WIRE; COLOR CODED THERMOELASTOMERIC BLOCK COPOLYMER OR EPR OR TPR OR ETHYLENE PROPYLENE COPOLYMER INSULATION WITH APPROXIMATE THICKNESS OF 0.015" AND WITH PREFERRED COLOR COMBINATIONSPAIR #1 WHITE AND BLACK, PAIR #2 WHITE AND BROWN PAIR #3 WHITE AND RED, OR BLACK, WHITE, RED, GREEN, ORANGE, BLUE, (STATE ALTERNATE COLOR CODES BID); BLACK THERMOELASTOMERIC BLOCK COPOLYMER OR EPR OR EP JACKET WITH THICKNESS OF APPROXIMATELY 0.032" AND WITH RIP CORD; CABLE APPROVED UNDER UL SUBJECT 13, CABLE PASSES UL-VW-1 AND IEEE-383 FLAME TEST; CABLE SUNLIGHT RATED. CABLE SUITABLE FOR INDOOR, OUTDOOR, AND UNDERGROUND (WET, DIRECT BURIED) APPLICATIONS. CABLE ALSO SUITABLE FOR CONDUIT, TRENCH AND CABLE TRAY APPLICATIONS. CABLE APPROXIMATE OUTSIDE DIAMETER OF 0.35 INCHES. CABLE SHALL BE IDENTIFIED WITH MARKINGS TO INCLUDE: SIZE AND TYPE OF CABLE AND MANUFACTURER; CABLE SUITABLE FOR USE IN 161 KV OR 69 KV UTILITY SUBSTATIONS, 15 KV METACLAD SWITCHGEAR UNITS, AND CONTROL BUILDING RELAY AND COMMUNICATIONS CABINET SUCH THAT 0 TO 1 MILLIAMPERE SIGNAL LEVELS FROM AMP, WATT, VAR, AND VOLT TRANSDUCERS ARE PROPERLY COMMUNICATED TO SCADA EQUIPMENT. CONDUCTOR TO BE FURNISHED ON STANDARD NONRETURNABLE REELS IN A CONTINUOUS LENGTH OF ABOUT 1000 FEET PER REEL. EACH REEL TO BE TAGGED WITH TOTAL FOOTAGE; TYPE OF CONDUCTOR, MANUFACTURER, GROSS, TARE, AND NET WEIGHT. SEQUENTIAL FOOTAGE MARKS SHALL BE CLEARLY PRINTED ON THE CABLE JACKET AT MAXIMUM INTERVALS OF FIVE FEET. SEQUENTIAL FOOTAGE MARKINGS SHALL BE DURABLE AND REMAIN LEGIBLE AFTER (3) YEARS OF EXPOSURE TO THE ENVIRONMENT. (CU 108082) LUG, COMPRESSION TYPE: RING TERMINAL WIRE SIZE: #12 - #10 AWG WIRE MATERIAL: COPPER BOLT SIZE: #10 BARREL: BRAZED SEAM ADDITIONAL DESCRIPTION: SOLDERLESS NON-INSULATED RING TERMINAL CONNECTOR, WIRE SIZE: 12-10 AWG STRANDED, STUD SIZE: #10, CONSTRUCTED OF ELECTROLYTIC COPPER FOR CONDUCTIVITY WITH A BRAZED SEAM BARREL.; (CU 0150317) SECONDARY URD CABLE--INSULATE ALL CONDUCTORS WITH 600 VOLT CROSS-LINKED POLYETHYLENE. ALL CONDUCTORS ARE CONCENTRICALLY STRANDED COPPER WITH CLASS B STRANDING PER AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) STANDARD B8. ASSEMBLE TWO (2) #4/0 AWG CONDUCTORS TOGETHER WITH ONE (1) #2/0 AWG CONDUCTOR. THE CONDUCTORS SHALL BE RATED WITH A MAXIMUM OPERATING TEMPERATURE OF 90 DEGREE CENTIGRADE IN EITHER WET OR DRY USE. COMPLY WITH UNDERWRITERS LABORATORIES (UL) STANDARD UL 854 FOR USE-2 CABLE OR UL 44 FOR RHW-2. UNIQUELY LABEL EACH CONDUCTOR. FURNISH THE CABLE ON A STANDARD NONRETURNABLE REEL WITH 1000 FEET PER REEL. TAG EACH REEL WITH TOTAL FEET, GROSS, TARE, NET WEIGHT, TYPE OF CONDUCTOR, NUMBER OF CONDUCTORS, AND MANUFACTURER.; 3-BOLT CLAMPING FLANGE FOR DURHAM CABINETS, 200-AMP WITH MOUNTING HARDWARE; SFP, TRANSMODE,2.4GIG, 1310NM, 2KM, TRX100007