Specifications include, but are not limited to: ● All permits and licenses necessary shall be secured and paid by the bidder ● Removal and disposal of all HVAC loop water piping and insulation ● Installation of new HVAC loop water piping and insulation ● Base Bid Contractor shall utilize schedule 40 black steel pipe. Fittings 2 ½” and larger shall be welded and fittings 2” and smaller shall be threaded. ● Alternate Bid, Contractor shall provide add/deduct price to utilize piping system as manufactured by Aquatherm. Contractor shall verify system quote in this alternate is listed for use on systems containing water and operating at a temperature of 200 degrees Fahrenheit and a system pressure of 125 pounds. ● Removal and replacement of electrical wiring and fixtures (base bid price should include the removal of 100- 2x4 fluorescent lay in fixtures and the purchase and install of 100- 2x4 LED flat panel 5000K fixtures) ● Ceiling tile and grid removal and replacement ● Provide onsite dumpster for discarded materials ● New insulation shall consist of 1” thick (“polyiso”) on pipe mains and 1” thick (K-Flex) on branch lines