Specifications include, but are not limited to: The Barrow County School System is interested in the following: a. Adding one CAT-6A data drop terminated in biscuit jack located above ceiling in blue highlighted locations on prints and as specified in the attached cable location spreadsheet. Cabling is to be used to connect Wireless Access Points. Adding CAT-6 data drops, terminated in existing gang boxes, for data connections in orange highlighted locations on prints and as specified in the attached cable location spreadsheet. Adding one CAT-6 data drop terminated in biscuit jack located above ceiling in green highlighted locations on prints and as specified in the attached cable location spreadsheet. Cabling is to be used to connect security cameras. The horizontal cabling system is based on the installation of 4-pair unshielded twisted pair (UTP) category 6 data cables, conforming to applicable ANSI/EIA/TIA/BICSI standards. Specifications for the Jacks and Outlets, Horizontal Wiring, and Patch Panels are provided in this document. The intent of this document is to establish the specifications and standards of the project. Specific products and model numbers are mentioned for the purpose of conveying design expectations. Comparable or equivalent equipment will be considered. Vendor is expected to provide new data racks/cabinets for cabling. Vendor will use existing cable tray (installed 2023) to support new cabling. Existing penetrations into classrooms may be used by vendor if dedicated solely to data cabling and available. Vendor is expected to provide additional patch panels as required, penetrations into classrooms if required, and J-hooks if/as required in classrooms...