Specifications include, but are not limited to: The successful proposer shall perform the following tests and calibrations on the electrical transmission, distribution and generation protection relays: 1.1 Verification of settings (current tap, time, dial, instantaneous, etc.) of the relay compared to previous test reports. 1.2 Minimum pickup testing and calibration as specified. Tests shall be performed in the specified taps. 1.3 Overcurrent relay timing curve testing and calibration to within five percent (5%) of the manufacturer’s timing curves. 1.4 Overcurrent relay instantaneous element testing and calibration to within three percent (3%) of desired setting. 1.5 Testing and calibration of other relay trip points and relay functions to within five percent (5%) of relay manufacturer’s specifications...