Specifications include, but are not limited to: The work shall consist of mobilization, transporting all equipment and personnel to the site(s) designated, providing the necessary traffic control in accordance with all applicable sections of the Manual on Uniform Traffic Control Devices (MUTCD), furnishing all materials necessary, installing the loop, conductor(s), sealant, conduit, and pull box portion of a loop vehicle detector system, in accordance with the New Mexico State Department of Transportation Standard Specifications for Highway and Bridge Construction, current edition. Saw Cuts - Saw cuts shall be made in pavement to the dimensions and shape detailed in the contract or by the District Engineer or their designee, using an abrasive cutting wheel concrete saw. Saw cuts shall be 2 ¼” to 2 ½” deep and approximately 3/8” wide. A 3/8” wide slot shall be used to install ducted loop wire. Two (2) inch diameter holes drilled at angle points to the same depth as the saw cuts shall be provided. Forty-five (45) degree angle cuts made at corners will be permitted in lieu of drilled holes. Sharp corners between overlapping saw cuts of over forty-five (45) degrees will not be permitted. Cuts across concrete pavement expansion joints shall also be drilled at this point to allow saw cuts across concrete pavement expansion joints for wire slack. Saw cuts shall overlap by a sufficient length to provide a smooth bottom and an even depth wire channel. When there is more than one (1) loop terminating at a pull box, each loop shall have a separate saw cut back to the box and saw cuts shall be as close as necessary to terminate wires. Prior to placement of the sealant and wire, the saw cut shall be cleaned of all debris and standing water by blowing out with compressed air. The pavement surface shall be damp to the touch. The inside of the saw cut shall be free from any sharp protrusions such as loose aggregate or uneven saw cuts. Loop detector wire shall be used for the installation in pavement saw cuts. All loop detector wire shall be No. 14 AWG stranded copper wire cross-linked polyethylene (XHHW) insulation conforming to the requirements of the International Municipal Signal Association (IMSA) specification (Current Edition). Ducted loop wire shall be used for insulation in pavement saw cuts or by directly overlaying with paving material. Ducted loop wire shall be loop detector wire loosely encased in polyvinyl chloride or a polyethylene 0.250 inch O.D. tube. All ducted loop wire shall conform to the requirements of the IMSA specification, current edition, except the interior No. 14 AWG stranded conductor may either be insulated with polyvinyl chloride with a nylon jacket (THHN) or polyethylene (XHHW). A continuous run of loop wire shall be placed in the saw cut wound around the coil section the number of turns shown in the contract or as directed by the District Engineer or their designee. No more than four (4) wires or turns shall be placed in a single saw cut. Loop detector wire pairs shall be twisted; four (4) to six (6) twists per foot, between the loop, through the lead-in saw cut and conduit, to the shielded lead-in splice. Each splice shall be soldered, scotch locked, and seal packed at locations relative to splices occurring in pull box and belding. Approx. Qty. UOM Article and Description; 200 Each 6x6 Magnetic Loop Detector -Complete in place with Conductors to pull box. (Saw cut, conductor's), sealant, 30 FT lead-in inclusive.) Lead-ins greater than 30 FT, Use bid item 012. 500 Each 6x30 Magnetic Loop Detector - Complete in place with Conductors to pull box, (Saw cut, conductor's), sealant, lead-in inclusive.) Lead-ins greater than 30 FT, Use bid item 012. 50 Each 6x40 Magnetic Loop Detector- Complete in place with Conductors to pull box, (saw cut, conductor's), sealant, 30 FT lead-in inclusive). Leadins greater than 30 FT, use Bid item 012. 50 Each 6x30 Quadrapole Magnetic Loop Detector - Complete in place with conductors to pull box, (saw cut, conductor's), sealant, 30 FT lead-in inclusive). Lead-ins greater than 30 FT, use Bid item 012. 50 Each 6X40 Quadrapole Magnetic Loop Detector- Complete in place with conductors to pull box, (saw cut, conductor's), sealant, 30 FT lead-in inclusive). Lead-ins greater than 30 FT, use Bid item 012. 150 Each Pull box Complete Installation- Including box, cover, conduit to controller cabinet and detector loops, all asphalt pavement, concrete pavement, or curb cutting, removal and patching. 500 L.F. 1” PVC Schedule 40 Conduit - Complete in place, including all asphalt pavement, concrete pavement or curb cutting and patching, trenching, conduit, and backfill. 5,000 L.F. 2” PVC schedule 40 Conduit -Complete in place, including all connections to pull box, all asphalt pavement, concrete pavement, or curb cutting and patching, trenching, conduit, and backfill. 5,000 L.F. 3” PVC schedule 40 Conduit - Complete in place, including all connections to pull box, all asphalt pavement or concrete pavement or curb cutting and patching, trenching, conduit, and backfill. 5,000 L.F. 3” HDPE Electrical Conduit - Complete in place (INSTALLED BY DIRECTIONAL BORE), including all connections to pull box, all asphalt pavement, concrete pavement or curb cutting and patching, trenching, conduit, and backfill.