Specifications include, but are not limited to: 1. When any Fire Alarm or Water flow alarm activation occurs the following sequence of events shall take place: A. First, the monitoring company shall call the CentralPlant On Duty Operator. The monitoring company shall provide the name of the building and state that a fire alarm activation has occurred. B. Second, the monitoring company shall call UNO Department of Public Safety & Security (UNODPSS). The monitoring company shall provide the name of the building and state that a fire alarm activation has occurred. C. Third, Central Plant Personnel & UNODPSS will investigate the alarm and if warranted UNODPSS will contact New Orleans Fire Department emergency response. D. Fourth, Central Plant On-Duty Operator and UNODPSS shall log the alarm event into their respective logs, providing information concerning location, result of investigation and whether NOFD responded. i. The fire alarm service provider, upon receipt of the alarm signal, shall be contacted by Central Plant, the responding technician shall report to Central Plant and sign in. ii. Upon completion of the work, the responding technician shall report to Central Plant, brief them on the status of the fire alarm system and sign out. 2. When any Supervisory Signal Activation occurs the following sequence of events shall take place: A. First, the monitoring company shall call the Central Plant On-Duty Operator B. The monitoring company shall provide the name of the building and state that a supervisory activation has occurred. i. Central Pant will respond to the building and log the supervisory issue and silence the alarm panel ii. Central Plant will contact the fire alarm service provider and report the supervisory status iii. Upon arrival, the responding technician shall report to Central Plant and sign in. a. Upon completion of work, the responding technician shall report to Central Plant, brief them on the status of the fire alarm system, and sign out...