Specifications include, but are not limited to: General Requirements: Mulit- voltage selector switch with 120/208v, 277/480v 3-phase and 120/240v 1-phase Kohler, Cummins/Onan, Caterpillar or approved equal Engine to be EPA certified to Tier 4 Final non-road standards Emergency stop switch Backlit LCD display Control panel with remote start/stop capability, NFPA 110 Cam lock barrel lugs and bus bar distribution panel Minimum 120 gallon sub-base dual wall fuel tank Sound-attenuating powder coated housing with quiet operation of not more than 75 dB(A) sound level DOT approved trailer with LET lights and pintle eye, spare tire, crank type leveling jacks and safety chains 12 VDC electrical system with batteries, rack, cables and battery charger Include start up fees, with batteries and 2 hour load bank test Install 120 volts for trickle charger from existing outlet Generator to have minimum 3 year warranty / 2000 hours and trailer to have minimum 1 year warranty / 3000 hours Warnings, Alarms and Statuses: Critical fuel level (alarm) ECM communication loss (shutdown) ECM diagnostics (alarm and shutdown) Fuel tank leak (alarm and shutdown) Speed sensor fault (alarm) Engine under speed (shutdown) High coolant temperature (alarm and shutdown) Low coolant temperature (alarm) Low oil pressure (alarm and shutdown) Overcrank (shutdown) Fail to crank Over/Under voltage (shutdown) KW overload (shutdown) Over/Under frequency (shutdown) Ground fault input (alarm) Emergency stop (shutdown) Input/output fault (alarm) Master switch not in auto (alarm) Battery charger fault (alarm) Generator running Common warning (alarm) Common fault (shutdown)