Specifications include, but are not limited to: Two (2) each – Pad mount distribution transformer, 300 kVA, 3-phase, 60 HZ, 95 BIL, and average temperature winding rise to 65 degrees C. The transformer shall include the following: a. 300 kVA rated b. 3-phase, 60 Hz c. Self-cooling, OA (Liquid filled) d. Primary (High Voltage) rated at 13,200Y/7,620 Volts, Wye-connected with neutral available and taps 2-2½% above and 2-2½% below. e. Secondary (Low Voltage) rated at 480/277 Volt, Wye-connected with neutral available f. Impedance of approximately 5% g. Loop feed h. Dead front; SPECIAL FEATURES a. Internal high-side fuse protection b. 200 Amp HV busing wells and inserts c. 10-hole blade (supported) LV bushings and neutral d. Housing with removable sill and compartment doors...