a. Conduct field drilling of two (2) 500ft test wells in order to perform a 48-hour thermal conductivity test to determine the potential ground loop capacity. i. See the specifications for well requirements to align with anticipated wells for final well field. ii. All testing shall conform with or exceed ASHRAE and IGSHPA standards, as applicable. b. Prepare a written report identifying test data and analysis provided by the proposing firm: i. Report shall clearly indicate the calculate Formation Thermal Conductivity of the Site, The Formation Thermal Diffusivity, Undisturbed Earth Temperature, and all other requirements from the Specifications to this RFP. ii. The report shall also outline/confirm the drilling process, materials and test equipment used, specific testing processes and methodologies used, testing timeframes, and site conditions before and after the testing (e.g., treatment of spoils, well plugging, etc). iii. Spot readings, testing logs, testing summaries, and calculations shall be provided. iv. Copies of relevant permits shall also be provided for Town records c. Provide additional documents as required per appended Specifications