Specifications include, but are not limited to: a. The Contractor shall use an amine-blend treatment product with distribution rates to control pH in the entire condensate system between 7.5 and 9.0. b. The following are parameters for program operation of the Chilled and Heating Water Closed Loops in the 515 E. Amite Building, Governor's mansion, 700 North State Street, Heber Ladner, Robert E. Lee, Central High, Woolfolk, William Winter, Bolton Building and Naval Reserve Buildings. c. The Contractor shall provide and maintain the following sodium nitrite concentration in these building systems. d. Heating Water loops at 1,000-1,500 ppm; and Chilled Water loops at 800-1,000 ppm. e. Treatment product should contain nitrite and TTA.