Specifications include, but are not limited to: Supplier agrees to the following Electrical System specifications: A. 100amp, 120/240V main distribution panel with external disconnect for incoming single phase service. B. Three (3) 2 fluorescent 4' bulb surface mounted strip fixtures with wire guards. C. One (1) 2-lamp emergency fixture above door. D. Twelve (12) 120v duplex receptacles with two receptacles per 20amp circuit. Receptacles will be mounted approximately 3' apart. E. Three (3) 120v GFI receptacles, each on a 20amp circuit. GFI receptacles will be exterior mounted. F. One (1) single-pole switch for lights. G. Wiring of HVAC unit. H. Prewired surface mount raceways. I. All electrical requirements stated shall meet the standards of the National Electric Code (NFPA 70) issued by the National Fire Protection Association. Supplier agrees that the HVAC unit must be a wall mounted one-ton unitary Bard HVAC unit model # W12AAAAO5XPXXXJ with 12,000 BTUH, 230/208A, single phase, 5.0KW heat strip, 2" pleated filter and remote manual digital thermostat. Thermostat will be mounted on the opposite wall of the HVAC unit. Supplier agrees that there must be two (2) 3" pass-throughs on the rear wall side, including flange and cap. Installed approximately 4' off the floor with waterproof, gasketed NEMA4 signal cable enclosures on the outside wall that include two 2" multi cable grommets/split cable glands for routing multiple pre-terminated cables outside of the shelter. Supplier agrees that two (2) Unistrut rails 10' long must be mounted on the exterior at the top and bottom of the rear wall...