Specifications include, but are not limited to: All Floors 5.1.2.1 New fixtures performance shall be a maximum of 35 watts for 2 x 4 fixtures and 18 watts for 1 x 4 fixtures, warmth 4000K, Viscor Lighting Products – Models: Bevel & CREB, 1 x 4 and 2 x 4 LED Fixtures. 5.1.2.2 Replacement fixtures must be the same fixture as what exists. Example: an air troffer fixture must be replaced with a suitable air troffer fixture. 5.1.2.3 Replace light switches and wireless switches that have on/off and dimming. Use Lutron Pico switches and Powpak. 5.1.2.4 Replace recessed lighting cans located in dry wall or ceiling tiles with RAB fixtures. Models: CRLEDFA, for all can lights. using 4000K warmth. (Note: Various bulb cases exist; type to be field-verified by the Contractor). 5.1.2.5 Mechanical Rooms - Retrofit existing fixture with T8 ballast ADV 10PA2P32N357 ELE Ballast (2) F32T8 120 277V Advance and Philips InstaFit LED T8. Existing on-off switch is to remain. 5.1.2.6 Bathrooms – On/off switch is to remain, and dual technology ultra-sonic and infrared occupancy sensors set to 30-minute delay using Lutron occupancy wireless sensor. 5.1.2.7 Classrooms, Conference Rooms, Offices, and Common Areas – On/off Pico switch with dimmer and occupancy sensor. 5.1.2.8 Convert stairwell lighting to LED by retrofitting existing fixture with T8 ballast ADV 10PA2P32N357 ELE Ballast (2) F32T8 120-277V Advance and Philips InstaFit LED T8. 5.1.2.9 Manufacture and model numbers are provided as a guide to performance and quality.