• System capacity: 30kVa/27kw 208V 3-Phase UPS system. • Input/output voltage: 208/120V (3W + N + G) – single or dual feed. • Redundant internal VRLA battery strings provide 11 minutes of runtime at full system load (30kVa), and 35 minutes of runtime at 12 kVa of load (.9PF). • Include extended runtime – external battery cabinet providing 80-90 minutes of runtime at 12kVa of load. o Equivalent battery power that is UL listed for data centers is acceptable with approval. • Include SNMP communications card with UPS and external battery cabinet. • Include 1-year parts & labor warranty to include UPS, batteries, 24x7 onsite start up service, PM’s. • Include 24x7 onsite startup of UPS by manufacture. • Include removal and disposal of existing UPS from customer dock. • Include dock to dock shipping. • Provide all spec sheets for UPS to include O&M’s, installation drawings, power requirements. • UPS manufacturer must have a (EOSL) end of service life grader than 15 years and supported OEM for same period of time from manufacture date. • All contractor employees must submit photo ID for background checks prior to project start. • All invoices must have all the specifics for the project listing on the invoice with dates.