Specifications include, but are not limited to: A. Furnish a totally native BACnet-based system, including the Microsoft compatible operator’s workstation, if a workstation is required. The operator’s workstation, all building controllers, application controllers, and all input/output devices shall communicate using the protocols and network standards as defined by ANSI/ASHRAE Standard 135–2008, BACnet. No gateways shall be used for communication to controllers installed under this section. Gateways may be used for communication to existing systems or to systems installed under other sections. B. Provide all necessary BACnet-compliant hardware and software to meet the system’s functional specifications. Provide Protocol Implementation Conformance Statement (PICS) for Windows-based control software and every controller in system, including unitary controllers. C. Prepare individual hardware layouts, interconnection drawings, and software configuration from project design data. Implement the detailed design for all analog and binary objects, system databases, graphic displays, logs, and management reports based on control descriptions, logic drawings, configuration data, and bid documents. D. Design, provide, and install all equipment cabinets, panels, data communication network cables needed, and all associated hardware. E. Provide and install all interconnecting cables between supplied cabinets, application controllers, and input/output devices. Provide and install all interconnecting cables between all operator’s terminals and peripheral devices (such as printers, etc.) supplied under this section. F. Provide supervisory specialists and technicians at the job site to assist in all phases of system installation, startup, and commissioning. G. Provide as-built documentation, operator’s terminal software, diagrams, and all other associated project operational documentation (such as technical manuals, logic, process & instrumentation drawings) on approved media, the sum total of which accurately represents the final system. H. Provide new sensors, dampers, valves, and install only new electronic actuators. No used components shall be used as any part or piece of installed system. I. DDC controls and communication wiring shall be installed in conduit maintaining an independent pathway and shall not share other disciplines/trades pathways.