Specifications include, but are not limited to: Need an Environmental Chamber for Individuals (up to 4 at a time) to work in. Of the 4 individuals chamber needs to be designed to meet below standards while two are exercising vigorously on ergometers which will be adding heat (from individual and ergometer) and humidity (from individual) to the internal space. • Exterior Dimensions: 21'10" (L) x 9' 4" (W) x 10' 6" (H) • Temperature Range: -10°C to 50°C • Humidifier/Dehumidifier o Relative Humidity Range: 20% to 95% as limited by a 4°C Dew Point • CO2 Scrubber or Equivalent CO2 removal system (Ventillation System) • Fresh Air Intake • Temperature Control Stability: ±0.2°C • Humidity Control: ±2% • Transition Rate: 0.5°C per minute average • Uniformity: ±0.5°C • Ceiling Conditioning • Door entry at least 36 inches wide on the width end • Window on outward facing wall to allow observation on the width end • Non-slip floor • Ramp entry or flush entry • Internal lighting • Complete installation • Inside panic alarm • Electrical outlets (both 115 and 220) inside chamber on each long wall o Two of each on each long wall • 3 Access ports with plugs (3 in) Port to allow wires/tubes to be connected to heat sensitive equipment outside of the chamber on the width end of the chamber • Digital control panel; -receive, unload and install furnished equipment. Includes any required equipment to unload and install. - dispose of trash and debris in dumpster provided by others - verify conditions of space prior to fabrication & installation - coordinate equipment requirements with architect and general contractor - vendor responsible for cost of repairs for any damages caused to facility by vendor