Specifications include, but are not limited to: The successful bidder will furnish all required engineering, material, and labor, including electrical connections or upgrades to the electrical feeder to the elevator and connections to fireman’s return and fire hat relay’s (relay provided by others). At completion of contract, the elevator will be a complete, fully functional, and working system that is ADA and ASME A17.1 compliant. The contractor will be responsible for obtaining permits and their associated costs, acceptance testing, and any other requirements imposed by the Oklahoma Department of Labor under the State Elevator Safety Act. Work shall include but not limited to the following base-bid items; New EC Pixel controller with solid state starter; New submersible pumping unit with Maxton valves; New complete in ground jack assembly with new pit channels; New Doors, Car doors and Hoistway doors. Stainless steel #4 finish; New MOVFE 2500 linear door operator. New Gal restrictive clutch, door hangers, door rollers, interlocks and door rails; Install new car guide shoe assembly’s Replace all limit switches; New wiring; Traveling cable spares: The traveling cable for the elevator shall have no fewer than eight spare conductors or ten percent spare conductors, whichever is greater. Car station spares: a minimum of eight spare conductors shall be supplied to the car station from the machine room. Communication wire: one pair of shielded communication wires shall be provided for an emergency phone, and one spare pair of shielded communication wires shall be provided in the traveling cable to the car. Other equipment spare wires: the number of spare wires shall be maintained regardless of other equipment installed inside the elevator at the time of installation, such as security card reader, camera, intercom, etc. Hoist way wire spares: There shall be no fewer than eight spare conductors from the elevator controller to the hoist way junction box; Provide extra pair of wires at hall stations for one card. Controller needs capability to connect to one card to lock out hall stations. Assist our IT department in installing card readers. Furnish and install a new Innovation control operating panel with code complaint fire service controls; Must have new Innovation hall position indictors with chime; Furnish and install new Innovation hall call stations; Furnish and installed barrel-type, key-operated switches and keys; EPCO1: for (e.g., lights, fan, independent service); EPCO2: for Run\stop switch; FEO K1: for fire service; Install hoistway access switch..