Specifications include, but are not limited to: Acceptable manufacturers: Kohler ONLY. Quantity: 1 – 52 KW generator with automatic transfer switch ____________________ Make: Please specify ____________________ Model: Please specify ____________________ The generator set shall be Standby Duty rated for the specified KW rating ____________________ The generator set shall be 52 KW STANDBY RATED, with an alternator rated for a Class B 80°C temperature rise or Class F 105°C temperature rise CONTINUOUS. It shall provide 65 KVA and 52 KW when operating at 120/ 208 volts, 60 Hz, 0.80 power factor STANDBY. The generator set shall be capable of a 130°C STANDBY rating while operating in an ambient condition of less than or equal to 104°F and a maximum elevation of 2,000 feet above sea level. The standby rating shall be available for the duration of the outage. ____________________ ____________________ The generator output shall be 52KW @ 1800 RPM 0.8 power factor, 208 V, 3-phase, 60 hertz dip of 20% ____________________ Vibration isolators shall be provided between the engine-generator and heavy duty steel base ____________________ The generator set shall be sound attenuated to a level suitable for a residential area