Specifications include, but are not limited to: LABOR: 1. Provide a single point of contact and coordination between manufacturer Eaton and University for the delivery, installation and integration of the UPS solution. 2. Disconnect, remove and dispose of existing (1) 30kVA Liebert NX UPS and (1) maintenance bypass cabinet with 480/208V transformer. 3. Reuse 60Amp Input breaker, conduit and conductors for input feed to new UPS systemReuse existing output feeder to electrical panel. 4. Provide UPS startup and support. 5. All services will be performed during normal business hours. 6. New UPS to be located in footprint of existing unit. 7. Provide all required terminations, testing and labeling of associated wiring with this scope of work. 8. As required, provide wiring permit fees from this scope of work. 9. All work must meet State of RI electrical, code and building requirements. EQUIPMENT AND SERVICES: - Supply and Install Qty: (1) Eaton 9355 Series Three Phase Online Tower UPS 30kVA/27kW, Single Feed, 208V/120V - 50/60Hz Hardwired In/Out w/ internal maintenance bypass 11 minutes internal runtime at full load - Qty: (1) 480V/208V Single Feed Input Isolation Cabinet with Maintenance Bypass - Eaton Industrial Gateway X-Slot Card - Eaton Environmental Monitoring Probe - 5X8 Start-Up Service