Specifications include, but are not limited to: Quantity 1 - Generac Industrial gaseous engine-driven generator, turbocharged/aftercooled 6 cylinder 14.2L engine, consisting of the following features and accessories: • SG0300GG20142S18PPSYG • Stationary Emergency-Standby rated • 300 kW Rating, wired for 120/208 VAC three phase, 60 Hz • Permanent Magnet Excitation • Natural Gas fuel system • Level 1 Acoustic Enclosure, Steel o Industrial Grey Baked-On Powder Coat Finish • UL2200 • Power Zone Digital Control Panel for Single or MPS Generators o Meets NFPA 99 and 110 requirements o Temp Range -40 to 70 degrees C o Humidity 2 – 95% (Non Condensing) o UL6200 o C-ETL-US o CE o FCC o IEC801 (Radiated Emissions, Susceptibility, and Surge Immunity) o 7” Resistive Color Touchscreen ▪ Built-in Webserver ▪ IP65 (front) ▪ Auto/Manual/Off key switch, Alarm Indication, Not in Auto Indication, audible alarm, emergency stop switch o Dual Core Digital Microprocessor ▪ RS485, Ethernet and CANbus ports