Specifications include, but are not limited to: Provide design and materials for a furnace, fume extraction hood, chimney stack and an emission control system in the not yet constructed Emmerson Fire lab on OSU’s Corvallis, OR campus. See below for more detailed specifications for the requested items. Equipment Group 1: Furnace and Furnace controls - Tilting Type Fire Test Furnace • Natural Gas fired. • 5MW capacity. • Capable of testing vertical and horizontal building specimens with integrated tilting mechanism. • Internal chamber size: 8’x4’x4’ (2.4m x 1.2m x 1.2m). Solution should include the following items: • Furnace switching and control system. o Data logging inputs/outputs. ~12 channels for instrumentation and sensors (not including thermocouples) and/or the ability to expand these outputs at a later date. • 2 view ports o Ports should allow for the use of a camera. Include pricing for an optional integrated camera system if applicable. If OSU decides it wants to add this item, pricing for it will be included when scoring pricing as noted in 7.8.4 but its inclusion will also be considered when scoring other sections. • Frames for lifting/mounting test specimens. • Explanation of how your system will accommodate future additions such as panel loading capabilities. via a 10-ton hydraulic actuator with 12” stroke. Provide cut sheets detailing: • Approximate equipment and operational dimensions including access to serviceable components. o Tilt operation • Location of utility connections such as gas, shop air. • Location of any required sensors such as thermocouples, or combustion gas probes. • Necessary floor connections and prep for equipment.